FireLite fire-rated glass - an innovative window solution that combines openness and security

FireLite is crafted from super heat-resistant glass-ceramics with an almost zero coefficient of thermal expansion, making it incredibly resistant to thermal shock. It won't crack, even when heated to 800°C and exposed to cold water. As the only fire-rated glass that withstands both intense heat during a fire and rapid cooling from firefighting efforts, FireLite offers unparalleled protection. Its exceptional fire resistance has been verified by meeting UL standards in the United States.

Features

●High thermal shock resistance

FireLite is a heat-resistant glass-ceramic with almost zero thermal expansion, making it the only fire-rated glass capable of withstanding temperatures up to 800°C. Its exceptional resistance to thermal shock ensures it won’t break, even when immediately exposed to water.

●Clear visibility without mesh

FireLite offers clear visibility nearly identical to that of standard window glass. When used to demarcate a fire compartment, it allows for a bright, open interior space.

●No risk of spontaneous breakage
photo of how heat-resistant tempered glass breaks

Unlike heat-resistant tempered glass, which can break unexpectedly even without external force, FireLite is free from this issue.

●Cutting process possible

Heat-resistant tempered glass is challenging to cut and process, with a high risk of breakage. In contrast, FireLite is easy to cut without these concerns.

Construction Examples

Size

Propeties

Properties FireLite Float glass
Visible light transmittance 5 mm thickness % 87 89
8 mm thickness % 85 88
Coefficient of thermal expansion 30~750゜C ×10-6/K -0.3 8.5
Specific heat 25℃ J/kg・K 710 753
Thermal conductivity 25℃ W/m・K 1.6 1
Specific gravity Approx. 2.5 Approx. 2.5
Young's modulus GPa 88 72
Poisson's ratio 0.24 0.23
Mohs hardness 700 650
  • The above figures are not guaranteed.
  • The float glass data is a typical reference value.
  • The coefficient of thermal expansion of float glass is 30 to 350°C.

Transmittance Curve

US UL Standard Test

The UL Standard, a leading U.S. safety standard, mandates that fire doors undergo testing for safety during fire extinguishing operations. This includes not only a heating test but also a water discharge test conducted immediately after heating to ensure that no significant defects occur during firefighting efforts. Following independent testing, FireLite was confirmed to meet this rigorous UL standard.